Data Center Water Use

Written by Dr. Vikram Lakhanpal
Published on April 8, 2026
Research Highlights

Data centers use a combination of energy intensive air cooling and water intensive evaporative cooling to remove heat from servers.

Up to 85% of the water data centers use evaporates and does not return to the water supply.

Higher temperatures and concentrations of dissolved solids in water returned to the supply impact drinking water, crops, and aquatic life.

Water cools data centers more efficiently than air.

Data centers are facilities that contain servers and computers that run online services, like cloud storage, cryptocurrency mining, and Artificial Intelligence (AI) programs (Leppert 2025, Offutt & Zhu 2025). As of April 2026, the U.S. has more than 4,000 data centers, 37% of the world’s total (Data Center Map n.d.). As AI and other operations require more processing power, data centers use more electricity and create more heat (Singer et al. 2024, Kim & Lee 2024).

Data centers directly consume water during cooling, and indirectly by using electricity (Ahmad 2024). Indirect water use depends on the type of fuel used for electricity and the power plant’s efficiency. Direct water use depends on how the facility approaches cooling. Some facilities use air cooling, where air conditioners blow cold air through the servers to carry the heat away (Shehabi et al. 2024). Others use evaporative cooling, where hot air from the server room is passed through a cooling tower containing water. The evaporating water absorbs heat, which lowers electricity used for cooling. However, the water vapor is lost in the process, creating a tradeoff between electricity-intensive air cooling and water-intensive evaporative cooling (Hershberg et al. 2025, Vertiv 2020). Data centers choose cooling systems based on factors including climate and resource availability.

Data centers consume up to 85% of the water they withdraw.

Withdrawal refers to the total amount of water used by a facility, while consumption is the amount of water not returned to the system. Data centers in the U.S. directly consumed 17.4 billion gallons of water in 2023, equivalent to roughly 160,000 American households (U.S. Environmental Protection Agency 2025, Shehabi et al. 2024). Annual direct consumption is projected to increase to between 38 and 73 billion gallons by 2028. Hyperscale data centers are expected to account for half of that water consumption. While definitions for hyperscale data centers vary, they typically contain at least 5,000 servers, take up more than 10,000 square feet of space, and can require more than 100 MW of power (Powell & Smalley n.d.). These projections vary based on expected developments in processing and cooling technologies, as well as construction and demand for data center services.

Some data center companies have published data on their water usage, though few have released information on individual data center consumption. Equinix, which operated 268 data centers worldwide in 2024, reported withdrawing 1.4 billion gallons and consuming 1.2 billion gallons, or 85% (Equinix 2025a, Equinix 2025b). Google reported their data center water consumption increased from 4.3 billion gallons in 2021 to 6.1 billion gallons in 2024 (Google 2025, Hölzle 2022). In total, the company withdrew 7.8 billion gallons of water in 2024, consuming 78%. Of 24 individual data centers in the U.S. and Canada, Google reported that nine withdrew less than 500,000 gallons per day, and three withdrew more than 2 million gallons per day (Google 2025, Figure 1). Their largest data center, located in Council Bluffs, IA, withdrew an average of 3.9 million gallons of water and consumed 2.8 million gallons per day.

Discharged cooling water can impact drinking water, crop yields, and aquatic life.

Research on how data center cooling affects water quality is limited. However, data center cooling systems are similar to those found in industrial facilities such as power plants and refineries, which can affect discharged water (Brown et al. 2025). Cooling water that returns to the water supply has a higher concentration of dissolved solids, such as calcium, chloride, and silica (Ahmad 2024). These can affect the taste of drinking water, lower crop yields, and be toxic to aquatic life (U.S. Geological Survey 2019, World Health Organization 2003). Increased salinity and temperature in discharge water may lower oxygen solubility and affect metabolism in freshwater wildlife (Khatib et al. 2025, Vengopalan et al. 2012). Legionella bacteria, which can cause Legionnaires’ disease in humans, can grow in improperly maintained cooling towers and spread through released water vapor (Centers for Disease Control 2025, Cejudo 2023).

See the Data Center Power Requirements and Addressing AI Energy Demands Science Notes for more information.

Figure 1. Distribution of water usage reported by Google data centers in the U.S. and Canada in 2024. The company reported water usage for 24 data centers. Sixteen of these withdrew fewer than 1 million gallons per day, while three used more than 2 million gallons per day. Out of the 7.8 billion gallons of water the company’s data centers withdrew in 2024, 78% was consumed due to evaporation during cooling and was not returned to the water system. Data from Google 2025.

References

Ahmad R (2024) Engineers often need a lot of water to keep data centers cool. Civil Engineering Source. https://www.asce.org/publications-and-news/civil-engineering-source/civil-engineering-magazine/issues/magazine-issue/article/2024/03/engineers-often-need-a-lot-of-water-to-keep-data-centers-cool

Brown M, Cline S, DeRosa A, Kenel P, Slabaugh R, et al. (2025) Cooling the cloud: water utilities in a data-driven world. American Water Works Association. https://www.awwa.org/wp-content/uploads/AWWA-Cooling-the-Cloud-Water-Utilities-in-a-Data-Driver-World.pdf

Cejudo CE, Pamintuan BC, Stoughton K, Whitfield M (2023) Emerging technologies review: water reuse systems for cooling tower applications. Pacific Northwest National Laboratory. PNNL-34788. https://doi.org/10.2172/2325011

Centers for Disease Control (2025) Controlling Legionella in cooling towers. https://www.cdc.gov/control-legionella/php/toolkit/cooling-towers-module.html

Data Center Map (n.a.) USA Data Centers https://www.datacentermap.com/usa/

Equinix (2025a) Equinix, Inc. Form 10-K December 31, 2024. https://investor.equinix.com/sec-filings/annual-reports/content/0001628280-25-005126/0001628280-25-005126.pdf

Equinix (2025b) Equinix 2024 sustainability data summary: Data sheet. https://www.equinix.com/content/dam/eqxcorp/en_us/documents/resources/data-sheets/ds_sustainability_data_en.pdf

Hershberg K, Burnett B, Roraff J, Hopker P, Brune M (2025) The energy & water use impacts of building system design for data centers: design considerations for Oregon & Washington. Columbia River Inter-Tribal Fish Commission. https://critfc.org/wp-content/uploads/2025/03/data-center-report.pdf

Google (2025) Environmental Report 2025. https://www.gstatic.com/gumdrop/sustainability/google-2025-environmental-report.pdf

Hölzle U (2022) Our commitment to climate-conscious data center cooling. The Keyword. https://blog.google/company-news/outreach-and-initiatives/sustainability/our-commitment-to-climate-conscious-data-center-cooling/

Khatib L, Pham A, Ahmed K, Frenkel VS (2025) Data centers and water: challenges and solutions for sustainable cooling. Journal AWWA, 117(8): 48-53. https://doi.org/10.1002/awwa.2504

Kim J, Lee H (2024) Computational study of thermal performance enhancement in high-energy density data center through immersive liquid cooling. International Refrigeration and Air Conditioning Conference. Paper 2601. https://docs.lib.purdue.edu/cgi/viewcontent.cgi?article=3600&context=iracc

Leppert R (2025) What we know about energy use at U.S. data centers amid the AI boom. Pew Research Institute. https://www.pewresearch.org/short-reads/2025/10/24/what-we-know-about-energy-use-at-us-data-centers-amid-the-ai-boom/

Offutt MC, Zhu L (2025) Data centers and their energy consumption: frequently asked questions. Congressional Research Service. R48646. https://www.congress.gov/crs-product/R48646

Powell P, Smalley I (n.d.) What is a hyperscale data center? IBM. https://www.ibm.com/think/topics/hyperscale-data-center

Shehabi A, Smith SJ, Hubbard A, Newkirk A, Lei Nuoa, et al. (2024) 2024 United States Data Center Energy Usage Report. Lawrence Berkeley National Laboratory. LBNL-200163. https://doi.org/10.71468/P1WC7Q

Singer B, Bingham DR, Corbett B, Davenport C, Gandolfi A, et al. (2024) GS SUSTAIN: Generational Growth — AI/data centers' global power surge and the sustainability impact. Goldman Sachs. https://www.goldmansachs.com/images/migrated/insights/pages/gs-research/gs-sustain-generational-growth-ai-data-centers-global-power-surge-and-the-sustainability-impact/sustain-data-center-redaction.pdf

U.S. Environmental Protection Agency (2025) How we use water. https://www.epa.gov/watersense/how-we-use-water

U.S. Geological Survey (2019) Chloride, salinity, and dissolved solids. https://www.usgs.gov/mission-areas/water-resources/science/chloride-salinity-and-dissolved-solids

Venugopalan VP, Rajagopal S, Jenner HA (2012) Operational and environmental issues relating to industrial cooling water systems: an overview. Operational and Environmental Consequences of Large Industrial Cooling Water Systems. https://doi.org/10.1007/978-1-4614-1698-2_1

Vertiv (2020) Calculating the impact of water usage on data center costs and sustainability. Vertiv White Paper. https://www.vertiv.com/4ad73a/globalassets/documents/white-papers/vertiv-water-usage-and-sustainability-wp-en-na-web_317594_0.pdf

World Health Organization (2003) Total dissolved solids in drinking-water. https://www.who.int/docs/default-source/wash-documents/wash-chemicals/total-dissolved-solids-background-document.pdf

Most Policy Initiative logo
Contact
238 E High St., 3rd Floor
Jefferson City, MO 65101
314-827-4549
info@mostpolicyinitiative.org
Organization
© 2026 MOST Policy Initiative | Website design and development by Pixel Jam Digital
Privacy Policy
chevron-down linkedin facebook pinterest youtube rss twitter instagram facebook-blank rss-blank linkedin-blank pinterest youtube twitter instagram